The stepladder at the 5ft section of the pool is loose. .2517; Ladders, steps, and handrails shall be properly placed and in good repair. Tighten ladder to prevent movement.
2.0
15.
Throw rope for the ring buoy was measured to be over 50ft long. .2530; The throwing rope shall be as long as one and one-half times the maximum width of the pool or 50 feet, whichever is less, attached to a U.S. Coast Guard approved ring buoy. Throw rope for ring buoy was reduced by CPO to be 50ft long. Points taken, permit issued due to immediate correction.
6.0
16.
Fences around the pool area are less than 48 inches. .2528; The top barrier shall be at least 48 inches above the grade measured on the side of the barrier that faces away from the swimming pool. Pool fencing constructed prior to 5/01/2010, current dimensions are in compliance with older pool rules. Fencing must comply with most recent pool rules if at least fifty percent (50%) of the fence has been damaged or destroyed or the owner or operator elects to replace the fence.
4.0
22.
At the start of the inspection, the emergency phone could not place outgoing calls. .2530; A telephone capable of directly dialing 911 or other emergency notification system shall be provided and accessible to all pool users. Phone was repaired during the inspection, allowing for outgoing, incoming, and dialing of 911. Points taken, permit issued due to immediate correction.
6.0
26.
A couple pipes were missing identifying labels. .2518; Exposed pipes and valves shall be identified by a color code or labels. Add labels to piping in equipment room.
0.0
General Comments
Wake County Plan Review and Recreational Sanitation Section recommends pools be hyper chlorinated at least twice a month. This activity should be accurately logged on the CPO check list form.
Some debris in skimmer baskets. Surface skimmer baskets shall be kept clean and in good repair. Clean skimmer baskets.
4.0
11.
Ladder in the 5ft section of the pool is loose and needs tightening. Ladders shall be properly placed and in good repair, adjust ladder.
2.0
16.
Fences around pool are less than 48 inches. The top barrier shall be at least 48 inches above the grade measured on the side of the barrier that faces away from the swimming pool. Pool was constructed prior to 2010, REHS recommends increasing the height of the fences.
4.0
24.
Observed flow rate: 225 gpm
0.0
General Comments
Wake County Plan Review and Recreational Sanitation Section recommends pools be hyper chlorinated at least twice a month. This activity should be accurately logged on the CPO check list form.
Some skimmer baskets had floating debris. Surface skimmers with weirs, baskets, and covers shall be clean, in good repair and functioning properly, with no floating debris. Clean skimmer baskets.
0.0
15.
Throw rope for ring buoy was observed to be greater than 50ft, 1.5x the length of the pool is greater than 50ft. A minimum of 1/4 in. diameter throwing rope as long as one and one-half times the maximum width of the pool or 50 ft, whichever is less, attached to a US Coast Guard approved ring buoy shall be conspicuously and conveniently on hand at all times. Throwing rope length reduced to be in compliance, points taken but operational permit NOT denied.
6.0
16.
General Comment: Pool was permitted May 2008. Pools permitted prior to 4/01/2010 with existing fences that do not comply with the current dimensional requirements shall not be denied an operation permit.
0.0
17.
Various chairs placed less than 6ft from edge of pool. Outdoor swimming pools shall provide at least six feet of clear walking space at all points of the pool deck or walkway. Move chairs and lounge chairs to provide this 6ft space.
4.0
24.
Flow rate observed: 200GPM
0.0
25.
General Comment: Observed minor green corrosion on grounding wire in pump room.
0.0
General Comments
Wake County Plan Review and Recreational Sanitation Section recommends pools be hyper chlorinated at least twice a month. This activity should be accurately logged on the CPO check list form.
Minor debris on pool floor. Pool walls and floor shall be kept clean, free of debris, and in good repair.
0.0
8.
Floating debris found in surface skimmer baskets. Surface skimmers shall be clean, in good repair, and functioning properly with no floating debris. Clean surface skimmers.
0.0
16.
Fences and gates measured to be 46 in. Pool was permitted May 2008. Pools permitted prior to 4/01/2010 with existing fences that do not comply with the current dimensional requirements shall not be denied an operation permit.
4.0
26.
Labels on pipes worn and illegible. .2518(d) Exposed pipes and valves shall be identified by color codes or labels. Put labels on pipes in equipment room.
2.0
General Comments
Wake County Plan Review and Recreational Sanitation Section recommends pools be hyper chlorinated at least twice a month. This activity should be accurately logged on the CPO check list form.
Wake County Plan Review and Recreational Sanitation Section recommends pools be hyper chlorinated at least twice a month. This activity should be accurately logged on the CPO check list form.
This pool must remain closed until the local and state closure orders currently in effect as a result of the COVID-19 pandemic are terminated.
No night swimming.
Pool staff and patrons are strongly encouraged to comply with the most current CDC guidance concerning social distancing related to the COVID-19 pandemic.
The lables on the valves in the pump room are faded. Valves and pipes shall be identified by color codes or labels.
2.0
General Comments
-Please ensure that the landscaping around the residents' fob gate is trimmed so that the magnetic strip on the gate latches properly. Wake County Plan Review and Recreational Sanitation Section recommends pools be hyper chlorinated at least twice a month. This activity should be accurately logged on the CPO check list form. -CPO: Michael Maldonado Wake 5318 exp: 12/11/23 NSPF: 618172 exp: 11/16/23 ckruger@poolprofessionals. com 919-787-7878
The pool floor has some debris. Pool walls and floors shall be kept free of debris. Please vacuum.
4.0
8.
The baskets and skimmers were observed with debris. Skimmers and baskets shall be kept clean.
4.0
26.
The valves and pipes in the pool room were not clearly labeled. Valves and pipes shall be identified by color codes or labels. Labeled during inspection.
2.0
General Comments
-No night swimming. -Please ensure that the back gate is locked at all times. Only the front gate and clubouse entrance should be used. -Permit issued.
Gate at the far entrance to the pool was remaining in the open position when opened fully. It was catching on the landscaping. correction: Rod was driven into the ground to prevent the gate from opening fully, keeping the gate off of the plants. . .
Gate to the Chemical storage room is not self-closing so shall remain locked.
4.0
29.
Shower had no water supplied. corrected
2.0
General Comments
Pool Closes at dusk. No Night Swimming. Permit expires October 31, 2016
#5: upon opening-Dan Clayton-Luce (#2198 WC); #21: Application indicates the pool is open from dawn to dusk.; GC: Delivered the DENR letter delivered to Dan Clayton-Luce (9:30 am)