"No Diving" markers were missing, state no diving symbol is not enough and the "NO DIVING" letters must be 4 inches tall. Fixed during inspection, but points still taken.
4.0
15.
Ring buoy was not long enough, but was fixed during the inspection. Points still taken.
6.0
24.
Keep an eye on the pump's flow as it is close to the minimum turn over rate for the pool. Ensure it has enough flow to turnover at least 4 times in a day.
0.0
25.
Forced air was not working and fixed during the inspection in the chemical room. Light not working in the pump room.
2.0
29.
Hot water greater than 110 F. Hot water should not be greater than 110 F.
2.0
General Comments
Wake County Plan Review and Recreational Sanitation Section recommends pools be hyper chlorinated at least twice a month. This activity should be accurately logged on the CPO check list form.
concrete starting to crack and break at pvc return in pump room.
2.0
General Comments
Wake County Plan Review and Recreational Sanitation Section recommends pools be hyper chlorinated at least twice a month. This activity should be accurately logged on the CPO check list form.
Wake County Plan Review and Recreational Sanitation Section recommends pools be hyper chlorinated at least twice a month. This activity should be accurately logged on the CPO check list form.
Wake County Plan Review and Recreational Sanitation Section recommends pools be hyper chlorinated at least twice a month. This activity should be accurately logged on the CPO check list form.
No recipient signature required due to covid restrictions. No night swimming.
Wake County Plan Review and Recreational Sanitation Section recommends pools be hyper chlorinated at least twice a month. This activity should be accurately logged on the CPO check list form.
2528; rule#8; There are 3 sliding doors in the club house that are required to be left unlocked by order of the fire marshal. The best fix is to install audible alarms on each sliding door. Ground level doors and windows opening from occupied buildings to inside the pool enclosure shall be self-closing or child protected by means of a barrier or audible alarm.
4.0
General Comments
Call me at 919-868-9244 when the sliding doors are fixed so I can come by and verify it has been done correctly. The alarms must be installed within one week.
Depth markings and NO DIVING markers are less than 4 inch letters (FDI)
4.0
16.
Electrical boxes at edge of pool deck are less than 45 inches from next horizontal member (10 Days to fix). Latch on gate closest the equipment room is less than 54 inches from the grounds surface (FDI). Door opening to restrooms does not properly self close/latch (FDI).
4.0
17.
Less than 8 feet of unobstructed walking space around the pool.
Running hot water temperature of bathroom fixtures was between 120 to 130 degrees F. Running hot water temperatures in areas accessible to the public can not exceed 110 degrees F. Adjust hot water flow to these fixtures A.S.A.P.
2.0
General Comments
Emergency phone is functioning correctly. 911 operators are showing the correct street address and phone number for the pool. 911 did not have the correct apartment complex name for the pool. Managers should contact 911 right away to provide the correct apartment complex name to emergency services. Seasonal pool permit for 2010 issued. Permit expires October 31, 2010. Pool is permitted for daylight use only. No night time swimming.