Facility



Forestville Elementary School


100 Lawson Ridge RD
KNIGHTDALE, NC 27545

Facility Type: Schools
 

Related Reports

Forestville Elementary School
Location: 100 Lawson Ridge RD KNIGHTDALE, NC 27545
Facility Type: Schools
Inspection Date: 06/09/2022
Score: 93

#  Comments Points
4. Repair toilets that have low water pressure and poor flow in the girls hall bathroom #122. Repair toilet that has poor water flow in the office staff bathroom #102K. Repair urinal that has poor water pressure and poor flow in the boys hall bathroom #113.Seal hole in divider wall between toilet stalls in girls hall bathroom #302. Repair nonfunctional toilet in the end stall of boys bathroom #304. 20.0
5. Repair nonfunctional hand wash sink faucets in bathrooms in classrooms #209 and #211. These sinks have no water flow for handwashing. (Priority repair of these sinks is needed.) Repair hand wash sink faucet valve handle in room #101D. This faucet control handle is stuck in place making it difficult to turn water flow on and off. 15.0
6. Repair roof and ceiling leaks in the hallway by room #104, in room #109, in room #202, in the cafeteria dining room #114, in the computer lab classroom #203, in custodial office room #118, in the art class kiln room #117B, and in staff bathroom #301. Water stained ceiling tiles should be replaced after the sources of these leaks are fixed. Repaint chipped and stained class bathroom walls for rooms #208, #212, #213, #215, #216, and #219. Wall covering is chipped and stained in classrooms #209 and #202. These classroom walls are in need of repainting. Six ceiling sprinklers for the fire suppression system in the building were missing the base cover caps. This leaves a hole in the ceiling around the sprinkler head. The sprinklers missing these base cover caps should be repaired. Replace missing ceiling tile in computer lab class room #203. Replace torn ground cover padding around the k-1 playground equipment. This torn ground covering could create possible trip and fall hazards if not repaired. 15.0
8. Ceiling vents in the media center are covered in dust residue and are in need of cleaning. Replace burned out light bulbs in ceiling fixture in boys bathroom #2304. 20.0
General Comments
Repair loose water fountain on sink in classroom #218. The braces that secures the climbing coils in a fixed position on the K-1 and 4-5 playground structures are broken. This poses safety concerns due to exposed areas of sharp metal on the broken base as well as a potential for pinch hazards at the break. Priority repairs for safety are necessary. Two of the support posts on the elevated swing steps on the K-1 playground structure have become detached from their embedded ground anchors. This poses safety hazards to children playing on these steps. Recommend that this play structure not be used by students until repairs have been completed and the structure is verified to be safe for use again by repair staff. Two sewer cleanout pipes on school grounds are missing cover seals. One of the clean out pipes is located in the courtyard lawn adjacent to the K-1 playground and the other is behind modular building #1. These uncovered pipes poses potential trip and fall hazards if not repaired. The potential for clogged sewage lines and sewage gas odors is also likely if the sewage cleanout pipes are not capped. Please repair.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Forestville Elementary School
Location: 100 Lawson Ridge RD KNIGHTDALE, NC 27545
Facility Type: Schools
Inspection Date: 11/20/2019
Score: 93.5

#  Comments Points
4. Repair toilets with low water flow in girls hall bathroom #122 (Two toilets), in boys hall bathroom #304 (one toilet), in boys hall bathroom # 2304 (one toilet), in girls bathroom #2302 (one toilet) and in class bathroom # 219. Repair clogged toilet in class bathroom #216. 20.0
5. Repair nonfunctional hand wash sink faucets in boys hall bathrooms #304 and #2304 15.0
6. Repair ceiling leaks in the media center, in the cafeteria dining room, in the stage area, in custodial offices #116 and in classrooms #105 and #109. (Mold growth is present in ceiling leak areas in cafeteria dining room. ) The source of all ceiling leaks should be repaired and water/mold damaged ceiling tiles replaced. 15.0
11. Repair loose hand rail on playground structure behind modular buildings. 15.0
General Comments
Replace missing back flow cap on mop sink faucet in custodial closet # 2300 B. Water is leaking out of the top of the faucet pipe. This mop sink faucet has low water pressure as a result.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Forestville Elementary School
Location: 100 Lawson Ridge RD KNIGHTDALE, NC 27545
Facility Type: Schools
Inspection Date: 08/25/2017
Score: 93

#  Comments Points
3. Room 304- The faucet outside this room has a detached front panel. Please re-secure this panel. 20.0
4. Room 412- Two toilets are out of order. Please repair. 20.0
5. Room 2302- Only two out of six faucets will turn on. Please repair broken faucets. 15.0
6. Gym classrooms 404, 406 and 407- The carpets are heavily soiled/stained. Please clean all these carpets. Floors must be maintained clean. 15.0
General Comments
Inspection made with custodian- Ruth Garcia
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Forestville Elementary School
Location: 100 Lawson Ridge RD KNIGHTDALE, NC 27545
Facility Type: Schools
Inspection Date: 01/19/2016
Score: 96.5

#  Comments Points
3. There was one water fountain that had low water pressure. All water fountains must have adequate pressure. 20.0
6. Clean the floors and walls in the classroom. Clean the carpet in the classrooms to remove the stains. Clean the walls in the restroom near the hand sinks to remove the soap build up. 15.0
8. Replace the blown light bulbs throughout the school building. Replace the blown light bulbs in the boys restroom on the second floor. Clean the blinds and window seals in the modular building. 0.0
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Forestville Elementary School
Location: 100 Lawson Ridge RD KNIGHTDALE, NC 27545
Facility Type: Schools
Inspection Date: 07/25/2013
Score: 96

#  Comments Points
6. Clean the floors and walls in the classrooms. Clean the floors and walls in the hallways. Some of the walls need to be painted. 30.0
7. Keep storage at least 15 inches above the ground to facilitate cleaning of the floor. 10.0
General Comments
CG. 8. Clean the blinds to remove the dust. Clean the window fixtures to remove the sider webs and dead bugs
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Forestville Elementary School
Location: 100 Lawson Ridge RD KNIGHTDALE, NC 27545
Facility Type: Schools
Inspection Date: 03/30/2012
Score: 94

#  Comments Points
4. The handwashing station, at the girls restroom 122, was not working. The handwashing station, at girls restroom 302, was not working properly. The toilet, in trailer 5, was not working properly. Unit would flush but not fill back up. 15.0
6. Corner wall damage and peeling paint found in classrooms 105 and 109. Scratched up/damaged wall by window of classroom 2308. The black piece, of the carpeted floors, in classrooms 2308 and 2309 were loose. This is a potential tripping hazard. Must be in good repair. Cracked corner wall for classroom 213. 15.0
7. Storage was on the floor in classrooms 109, 2314, art room, trailer 1, and trailer 6. Storage is to be at least 15 inches off of the floor. 10.0
8. Clean the dead bugs of the light shield in the hallway of the 2nd floor. Dust build-up on some of the ventilation untis located in the library and music room. Clean the vents in classrooms 309 and 306. 20.0
General Comments
3. Clean the build-up on the opening of the taller water fountain located in the kindergarden hallway. Clean the water fountain on the second floor hallway.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Forestville Elementary School
Location: 100 Lawson Ridge RD KNIGHTDALE, NC 27545
Facility Type: Schools
Inspection Date: 06/14/2010
Score: 97

#  Comments Points
4. the bathrooms inside classrooms have acoustic tile ceilings; all bathroom ceilings need to be non-absorbent and washable ( use same ceiling tile type as in the kitchen ); re-caulk the commodes as needed ( many commodes in Kindergarten have stained or shrinking caulking ) 15.0
6. the carpet needs to be cleaned ( some stains may be permanent ); repair base coving in 210; the floors around the commodes in Kindergarten are stained 15.0
7. provide dunnage racks in the storage room to keep heavy, large items off the ground ( pallets are not suitable for this purpose since you cannot clean under a pallet ); all bottom shelves of storage units need to be high enough off the ground to allow for floor cleaning under the shelves; room 2307 needs additional storage racks 0.0
General Comments
GC # 3 : hand sink fountain combination sinks in use ( possible contamination of fountain part when hands are washed ) ;
GC # 5 : the hand sinks in the boys room on the second floor are not working ( work order was placed )
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Forestville Elementary School
Location: 100 Lawson Ridge RD KNIGHTDALE, NC 27545
Facility Type: Schools
Inspection Date: 06/04/2009
Score: 94

#  Comments Points
3. several classrooms have hand sink/fountain combination sinks; the fountains at these sinks need to be adjusted ( water pressure is too low ); 20.0
4. the bathrooms inside classrooms have acoustic tile ceilings; all bathroom ceilings need to be non-absorbent and washable ( use same ceiling tile type as in the kitchen ) 15.0
6. the walls will need to be painted soon; the carpet needs to be cleaned; repair a hole in the wall behinfd the door to the kitchen in 109; dust the high ledges in the gym and the staircases 15.0
7. provide dunnage racks in the storage room to keep heavy, large items off the ground ( pallets are not suitable for this purpose since you cannot clean under a pallet ); remove any storage out of the bathrooms in the Kindergarten classrooms 10.0
General Comments
GC # 8 : dust the blinds ;
GC # 11 : please remind teachers not to lave any chemicals including cleaners, disinfectants, and air fresheners within reach of children; store chemicals in a locked cabinet or at least 5 feet off the ground
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Forestville Elementary School
Location: 100 Lawson Ridge RD KNIGHTDALE, NC 27545
Facility Type: Schools
Inspection Date: 06/23/2008
Score: 94

#  Comments Points
3. adjust fountain pressure in 213 and 217 20.0
4. the bathrooms inside classrooms have acoustic tile ceilings; all bathroom ceilings need to be non-absorbent and washable ( use same ceiling tile type as in the kitchen ) 15.0
6. the carpet is starting to show signs of wear ( permanent stains; seams are starting to show; transition strips to tile floor are loose in a few spots ); rocking chairs are causing damage to the walls; repair base coving in 217 and under the fountains near 127; paint the wall in the back of the stage 15.0
7. additional storage racks are needed in 202 and 118 to keep all storage 15 iches off the floor; several storage racks have a bottom shelf barely 2 inches above the ground; raise the bottm shelf high enough to allow for cleaning under the shelves; remove storage out of bathroom in 219 10.0
General Comments
GC # 3 : hand sink/fountain combination sinks are in use ( possible contamination of fountain part every time hands are washed ) ;
GC # 4 : re-caulk the commodes inside the classrooms ;
GC # 8 : dust the blinds and higher window sills
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Forestville Elementary School
Location: 100 Lawson Ridge RD KNIGHTDALE, NC 27545
Facility Type: Schools
Inspection Date: 04/09/2007
Score: 96

#  Comments Points
4. all bathroom ceilings need to be non-absorbent and washable ( use same ceiling tile type as in the kitchen ) 15.0
6. repair hole in the wall in 127 and re-attach baseboards in 208 15.0
7. additional racks are needed to keep all storage 12 iches off the floor; remove storage out of bathrooms ( Kindergarten ) 10.0
General Comments
GC # 3 : hand sink/fountain combination sinks in use ( contamination of fountain part during handwashing );
GC # 8 : dust vent covers, mini blinds, and windows ; several light shields are not closed completely;
GC # 11 : remind teachers to keep all chemicals ( this includes Chlorox wipes and Lysol spray ) out of reach of children !

Note : sewer clean-out outside of window in 306 is damaged