Location: 1018 E DAVIE ST RALEIGH, NC 27601-1624 Facility Type: Schools Inspection Date: 06/07/2024
Score: 88
#
Comments
Points
3.
Repair nonfunctional drinking fountain adjacent to the boy`s bathroom that is across the hall from custodial closet #131. This fountain has poor water pressure.
20.0
4.
Repair nonfunctional toilets in the following school locations: in the girl`s bathroom across the hall from staff bathroom #129, (one nonfunctional toilet), class bathroom #102A, (one nonfunctional toilet), in class bathroom 117A, (one nonfunctional toilet), in boy`s bathroom #203, (two nonfunctional toilets), in girl`s bathroom #213, (two nonfunctional toilets), in boy`s bathroom #113, (one nonfunctional toilet), and in girl`s bathroom #111, (two nonfunctional toilets). A total of ten toilets were nonfunctional in the school building at the time of inspection. Repair water damaged and deteriorated lower wall in staff bathroom #112A.
35.0
5.
Repair loose and broken hand wash sink faucet in girl`s bathroom #213. Repair clogged hand wash sink drain in classroom #210. Repair nonfunctional hand wash sink in classroom #104.
15.0
6.
Repair active ceiling leak in classroom #119 at the windows. Water was dripping into the classroom from the ceiling at the time of inspection. Basement classroom #B01 and the front entry door breezeway on the 100 hallway by the original stairway are flooding during heavy rainfall. Rainfall runoff from the roof should be diverted away from the building foundations in these locations to prevent the interior flooding. Example: Gutters with downspouts and downspout extensions can be used to redirect rainfall runoff away from the building foundation and into existing storm water drains. Repair ceiling leak on the hallway adjacent to the media center and over the entry ramp. Repair major roof and ceiling leaks in classroom trailer #4. Repair and repaint water stained and water damaged wall surfaces beneath the location of a prior roof leak at the cafeteria dining room windows. Repair and repaint chipping ceiling surfaces in the gym. Repair leaks on ceiling pipes over the gym entrance area. Priority repairs of these leaks are needed to prevent student and staff trip and fall hazards which could be caused by puddles of water on the gym floor forming beneath the dripping ceiling pipes. The surfaces of these ceiling pipes also have possible mold residue from the leaks and should be cleaned to remove the residue. Repair loose entry ramp side hand railing on trailer #5. This is a safety hazard since the loose ramp railing could collapse under use creating possible injury hazards. Replace rotted step board on side entrance deck for the orchestra trailer #6. Replace loose step board on front entrance deck into the orchestra trailer #6. Replace loose floor boards on the front entrance ramp into the orchestra trailer #6. Priority repairs are necessary on trailer #6 since these deteriorated or loose steps and loose ramp floorboards could cause possible injury from trip and fall hazards or from collapse under use. Reattach loose sink cabinet doors in classroom #119. Repair loose drop ceiling grid in classroom #120.
15.0
8.
Repair major leak on air conditioning system ceiling vent in the front entry breezeway on the 100 hallway adjacent to the courtyard entrance. This leak was actively dripping at the time of inspection. Priority repairs are needed for safety and health of students and staff to prevent possible slip and fall hazards from the water dripping from the overhead leak and to prevent possible areas of interior mold growth. Repair two loose ceiling light brackets in the gym. These loose ceiling light brackets pose a possible safety concern if they were to fall.
20.0
11.
There is a crack in the interior entry of the slide attached to the elevated platform of the tallest playground structure on the 100 hallway side of the building. Priority repairs to seal this crack on the slide are needed for safety.
15.0
General Comments
A wasp nest was present inside of the school greenhouse in the center courtyard. Pest control treatments are needed to remove the wasp's nest. Recommend keeping students and staff out of the greenhouse until the wasp nest is removed. The grounds in the interior courtyard are in need of trimming by the landscape contractor. The grass in the courtyard is roughly seven to eight inches high.
Location: 1018 E DAVIE ST RALEIGH, NC 27601-1624 Facility Type: Schools Inspection Date: 06/01/2023
Score: 85
#
Comments
Points
3.
Repair nonfunctional drinking fountain in the hallway by custodial closet #145.
20.0
4.
Repair clogged and nonfunctional toilet in girl`s hall bathroom #111. Repair torn wall pipe covering in the gym bathroom #306B. There is exposed insulation at this torn pipe covering. Repair clogged toilet in the end stall of the girl`s bathroom on the #100 hallway across from custodial closet #131. Repair toilets in classroom bathrooms #118A and #120A. Both toilets have poor water flow for flushing. The upper wall in classroom bathroom #102A has water/rust stains from a prior leak. This bathroom wall requires repainting with a waterproof and mold resistant paint. Repair clogged and nonfunctional toilet in the end stall of boy`s bathroom #203. Repair broken metal door frame in entry to class bathroom #104A. The bottom section of this broken door frame has sharp and rusted edges and requires repairs for safety. Repair clogged and nonfunctional toilet in the end stall of girl`s hall bathroom #213. Repair nonfunctional toilet in the dance studio classroom #123. This toilet needs a new flush valve due to poor water flow.
35.0
5.
Repair broken and nonfunctional handwash sink faucet in the girl`s hall bathroom #213. Repair plumbing for nonfunctional handwash sink faucets in classrooms #117 and #118. Priority repairs for hygiene are required since these are classrooms with restrooms that are lacking functional sinks for handwashing. Repair leaking faucet on mop sink in custodial closet on the #100 hallway. Repair leak on the base of handwash sink faucet in classroom #105A. The handwash sink in the guidance office bathroom #106A has poor water flow for handwashing ad requires repair.
15.0
6.
Repair and repaint chipping ceiling cover in the school gymnasium. Repaint water and rust stained corner wall by windows in the school cafeteria. The stained wall is located beneath the site of a prior roof leak. This area should be repainted with a waterproof and mold resistant paint. Classroom #B01 floods at the base of the wall by the windows during heavy rainfall. Drainage diversions are needed at the building foundation outside of this classroom to carry stormwater runoff away from the building. Major roof leaks are present in trailer #4. The trailer roof should be sealed to stop water entry. The water-stained ceiling inside of this trailer should be repainted with a waterproof and mold resistant paint. Repair leaking gutter over the entry door into trailer #4. Repair damaged wall by entry door and replace broken interior door frame in trailer #5. Carpet in the media center and in classroom #206 are covered in permanent stains and require replacement. The trailer sub floor at the side exit door inside of trailer #6 is deteriorated and is sagging under foot. This flooring requires priority repairs for safety due to the possibility of collapse. Replace splintered and deteriorated handrails on both side entry ramps and steps of trailer #6. Priority repairs for safety are necessary. Reattach or remove broken off wall cabinet door in classroom #106. This large cabinet door is currently detached and could fall over onto a student going to the restroom if left in place. Repaint chipped wall covering at the ceiling in classroom #215. Repaint peeling hallway wall coverings on the top floor hall across from girl`s bathroom #213 and in the main ground floor hallway adjacent to the lobby front entrance. Original building stairway to cafeteria has chipped handrailing. This handrail requires repainting and sealing coating.
15.0
7.
Large quantities of school equipment and supplies was stored in the class bathroom of trailer #1. The former special needs class bathroom #128A was filled with chairs for classrooms. The guidance office bathroom #106A stall had shelves of school storage. Bathrooms and bathroom floors are not clean storage locations. Class items stored in bathrooms can become a means of transfer for communicable disease pathogens including stomach flu. This storage in these bathrooms is also an impediment to the cleaning and repair of these facilities. If plans are to permanently convert the trailer #1 bathroom and bathroom #128A into storage locations the toilets should be removed from these restrooms and the sewage drainpipes for the removed toilets should be capped over. The school supplies in the guidance office bathroom #106A toilet stall should be removed.
20.0
8.
Repair ten nonfunctional ceiling light fixtures in the classroom of trailer #6. Repair leaking and nonfunctional air conditioning unit in classroom #104. Repair nonfunctional air conditioning unit in classroom #104A. Priority repairs of the air conditioners in both classroom #104 and #104A are necessary for the health and comfort of students and staff in these classrooms. Repair leaking air conditioning unit in classroom #102A.
20.0
11.
The deteriorated and abandoned greenhouse in the courtyard has broken and missing ceiling sections with pieces of metal ceiling framing hanging within. The greenhouse is also filled with junk and debris. The greenhouse in its current state poses safety concerns and possible injury hazards to students and staff. It should be locked shut to keep students out. Due to its poor state the greenhouse should either be renovated or demolished and removed from the school premises. The grounds of the courtyard are also overgrown and require trimming to prevent pest issues. The mesh fence top railing has become detached on the kindergarten playground fence adjacent to the parking lot. This fence railing should be reattached to prevent pinch hazards if students were to reach between the top rail and adjacent support post. The broken wooden cistern platform leaning against the exterior wall of trailer # 5 has exposed nail points jutting out. This poses possible injury hazards for students walking and playing by it. The cistern platform should either be repaired or removed from the school premises. Wooden pallets left by delivery staff on the grounds by the rear building entrance should be removed. This stack of pallets at the base of the building can create pest harborage issues.
25.0
General Comments
Cleaning chemicals, chemical surface wipes, and aerosol spray disinfectants were left out in areas accessible to students in classrooms throughout the school. Cleaning chemicals and aerosol spray cans should be stored in areas only accessible to school staff including in closed or locked cabinets.
Location: 1018 E DAVIE ST RALEIGH, NC 27601-1624 Facility Type: Schools Inspection Date: 03/10/2022
Score: 93
#
Comments
Points
4.
Repair nonfunctional toilet in boys bathroom #113. Repair nonfunctional toilet in staff bathroom #103B. Repair nonfunctional toilet in girls bathroom #213. Repair leaking toilet in the third stall of girls hall bathroom by staff room #129. Repair nonfunctional toilet in the second stall of girls hall bathroom by staff room #129. Repair leaking toilet in the first stall of the boys hall bathroom at staff room #129.
20.0
5.
Repair clogged and nonfunctional sink in the art classroom #124.
15.0
6.
Repair roof and ceiling leaks in trailer/modular class building #4. Repair or replace the water stained ceiling materials in this trailer after the sources of these leaks are fixed. Hand railings in both the northwest and northeast original stairways in the building are chipped and scraped and require repair and repaint. Water pipe along wall in the gym student bathroom #306B has a torn insulation cover at the base and should be properly rewrapped and sealed.
15.0
7.
Lost and found clothing for students was left in a pile on the floor of the bathroom for room #128. Class supplies and file cabinets were stored in the bathroom for the band program modular class building/trailer #5. Bathrooms and bathroom floors are not clean storage locations. Items stored in bathrooms can become a method of transfer for communicable disease including norovirus and stomach flu. The storage of these items in bathrooms is also an impediment to the cleaning and repair of these facilities. Please remove.
Location: 1018 E DAVIE ST RALEIGH, NC 27601-1624 Facility Type: Schools Inspection Date: 10/12/2020
Score: 94
#
Comments
Points
4.
Repair nonfunctional toilets in girls hall bathroom #213 and in class bathroom #120A. Repair clogged toilet in class bathroom #105A. Repair nonfunctional urinal in the boys hall bathroom #113. Repair broken toilet in office staff bathroom #125A.
20.0
5.
Repair leaking hand wash sink faucet valve in classroom #104. Replace broken paper towel dispenser in dance classroom #123.
15.0
6.
Repair ceiling leaks in the hallways by rooms #109 and #105A. Repair ceiling leaks in modular class buildings #3 and #4. Replace water damaged ceiling tiles after repair of leaks is completed.
15.0
7.
Excessive storage of classroom/student supplies and equipment was present in the following facility bathrooms: modular building bathroom # R-202-03, modular building #5 class bathroom, guidance office bathroom #106, and in the special needs class bathroom #128A. Bathrooms are not clean storage spaces. The storage of supplies and equipment in bathrooms is an impediment to the cleaning and repair of these facilities. Please remove the storage from these bathrooms.
Location: 1018 E DAVIE ST RALEIGH, NC 27601-1624 Facility Type: Schools Inspection Date: 02/11/2020
Score: 93
#
Comments
Points
3.
Repair drinking fountain that is nonfunctional on second floor hallway.
20.0
4.
Repair chipped wall coverings in girls bathrooms #111 and #213. Repair nonfunctional urinal in boys bathroom # 113. Repair nonfunctional toilets in girl bathrooms #111 and #203.
35.0
6.
Repair roof leak in second floor hallway at bathroom #213. Repair damaged plaster wall area beneath this same leak. The damaged wall covering in this location should be sealed and repainted.
Location: 1018 E DAVIE ST RALEIGH, NC 27601-1624 Facility Type: Schools Inspection Date: 09/18/2018
Score: 90.5
#
Comments
Points
4.
Repair nonfunctional toilets in girls restroom on first grade hallway and in main hallway for girls restroom #111. Repair nonfunctioning toilets in class bathrooms # 101A and #105A.
20.0
6.
Repair ceiling leaks on second floor hall outside of classroom # 202. (Replace water damaged ceiling tiles after leaks are repaired.) Repair water damaged wall above windows in classroom # 217. Repair chipping ceiling cover in gym instructors office.
15.0
7.
Classroom supplies and a refrigerator was stored in special needs class bathroom # 128. Excessive class item storage was also present in bathrooms for classroom # 143, #118, and in modular class bathrooms for band and enrichment classes. Bathrooms are not clean storage areas. If the special needs class bathroom # 128 and the enrichment modular bathroom are being converted into storage rooms the toilets in these bathrooms must be removed and the toilet drain pipes capped over.
10.0
8.
Repair loose hanging light ballast in orchestra modular classroom. Dust buildup was present on student bathroom ceiling vent in orchestra modular building. Replace air conditioning system vent filters in this building to prevent dust residue build up. Repair nonfunctional air conditioning system in chorus modular class building.
20.0
11.
Clorox and Lysol chemical surface wipes, Lysol aerosol spray cans, and other cleaning chemicals were left out in areas accessible to students in classrooms throughout the building. Cleaning chemicals and aerosol spray cans must be stored in areas not accessible to students. Examples: Store cleaning chemicals and aerosol spray cans in locked cabinets, drawers, and closets.
30.0
General Comments
Repair damaged swing rope on fourth and fifth grade playground equipment.
Location: 1018 E DAVIE ST RALEIGH, NC 27601-1624 Facility Type: Schools Inspection Date: 09/25/2017
Score: 92
#
Comments
Points
4.
on the 100 hallway boys bathroom: 2 urinals and one toilet was out of order. These need to be repaired. On the kindergarten/first grade hallway: in the girl`s bathroom, the toilet seat is loose and needs tightening in the 4th stall from the doorway. In the staff bathroom #129 the cabinet door handle is broken and loose. This needs repair.
20.0
5.
on the second floor in the staff bathroom, there is a pipe leaking under the sink that needs repair.
15.0
6.
paint is peeling on the walls outside of the cafeteria. In room 203, boys bathroom, the wall needs to be repaired behind the toilet in the 5th stall from the doorway. In the computer storage room 208: there is peeling paint that needs repair.
15.0
11.
Room 102,103B bathroom,106A, 107: hand sanitizer not 5 ft. up. In room 105A: a container of reabsorb chemical and sanitizer was stored underneath the sink which is not out of reach. In room 133 (art): comet, flame retardant, glass cleaner, shaving cream, exterior acrylic latex paint, interior/exterior latex paint and Clorox wipes were in a cabinet underneath the sink which were not out of reach for children. In room 134: spray paint primer was seen in a lower cabinet, In room 138: laundry starch was stored in a lower cabinet, In room 143: sanitizer/bleach wipes were in a lower cabinet, In the pre K room: supersorb chemical a container of bleach and Lysol spray were in lower cabinets not out of reach. In room 215: all purpose cleaner, pine glo chemical and dry erase board cleaner were not out of reach. In room 205-A: supersorb was in a cabinet not out of reach, The coaches office which was open in the gym had many containers of Clorox wipes on the desk and not out of reach. All of these items seen today must either be locked or kept out of the reach of children.
30.0
General Comments
some of the mats in the gym area are torn and need replacing.
Many chemicals/hazardous items seen today in many classrooms/storage areas were not stored out of the reach of children. Please remind staff that these products must be either stored out of reach or locked up to protect children.
Location: 1018 E DAVIE ST RALEIGH, NC 27601-1624 Facility Type: Schools Inspection Date: 07/21/2015
Score: 85.5
#
Comments
Points
3.
A. Drinking fountain is not working on the 2nd grade hallway. B. Increase the water pressure to 3 drinking fountains by boy`s restroom on the 1st grade hallway.
20.0
4.
Broken toilets located in the boy`s restroom in the 1st grade hallway and in the girl`s restroom located in the main hallway on the first floor, repair.
20.0
5.
A. Gym hand sink is dirty. Hand sink is not working in room 135, repair.
15.0
6.
Deteriorating paint on the window sills located in room B02. Chipping paint on the walls in the following areas: room 202, wall in room B06, wall in the hallway in the basement floor, room 212, room 217 and gym. Plaster is coming off the wall in the gym storage closet by the stage and in room 104. Worn wall in the 3rd grade breezeway by the stairs. Hole in wall by window in room 103. Cracked wall in room 143,room 135, and in room 119. Paint is chipping in big chunks on the ceiling located above the hand sink in the gym restroom. Stained carpeting in rooms 202,205,217, 104, 103C, 135,130 and in the library. Worn tape on carpet in room 103. Stained/dirty floor tile in room 103C. Floor tile is worn in the following areas: room 202, 2nd floor stairway that leads to the 3rd grade hallway, hallway by boy`s restroom in the main hall, 1st floor. Floor tile is missing under stairway in the 3rd grade hallway. Stair treads are missing on the stairway in the 3rd grade hall to 2nd floor. Water damaged ceiling in room 143 and in the 3rd grade hall breezeway.
30.0
7.
Keep all storage off the floor in the following storage closets: located in room 217 and in room 104. Storage in the gym restroom.
10.0
8.
Warped and dirty HAVC vents on the wall in the gym and in room 205, replace and clean.
20.0
11.
C. Carpet cleaner is on the floor of library in a large sprayer. Store chemicals locked in a cabinet or closet or at least 5 feet off the floor when not in use.
Location: 1018 E DAVIE ST RALEIGH, NC 27601-1624 Facility Type: Schools Inspection Date: 02/10/2015
Score: 87.5
#
Comments
Points
3.
B. Increase the water pressure to the 3 drinking fountains by boy's restroom on the 3rd grade hallway.
20.0
4.
A. Holes in wall in the last stall of boy's restroom located on the 2nd floor. Worn wall in the last stall in the girl's restroom on the 2nd floor. B. A urinal is broken in the boy's restroom located in the K-2 hallway, repair. A toilet is not working in the girl's restroom located in the K-2 hallway, repair.
35.0
6.
Areas of peeling paint are present in original building on classroom wall in room 109(D side wall), window sills in room B06, Kindergarten class room 117 door casing to hallway, and room 117 restroom door casing, restroom door casing in Kindergarten classrooms 118 and 119, door casing to room 103( Kindergarten), exterior door casing room 143 (Kindergarten). Keep children that are under six years old away from areas of peeling paint due to the possibility of exposed areas of lead based paint. Children in these classrooms should wash their hands frequently to avoid possible contact with lead dust especially before snacks and meals. Hole in the wall in the first floor hallway by the drinking fountain by the girl's restroom, repair. Room 101 has water damaged ceiling tiles, repair.
30.0
7.
B. Keep all storage off the floor in the following storage closets: gym closet, 105C and B, 135A, and 127.
10.0
11.
Store chemicals in locked cabinet or stored at least five feet off floor. Lysol spray, disinfecting wipes, hand sanitizer.
Location: 1018 E DAVIE ST RALEIGH, NC 27601-1624 Facility Type: Schools Inspection Date: 12/12/2013
Score: 90.5
#
Comments
Points
4.
Toilet in last stall boy's 1st grade hall bath loose. Secure to floor. One urinal out of order in 3rd grade boy's hall bath. One toilet out of order in 4th/5th grade Girl's hall bathroom. Detail clean around toilets around where lid attaches to base.
20.0
5.
Repair loose handsink basin in 4th/5th grade hall girl's bathroom. Detail clean handsinks in 4th/5th grade hall boys bathroom.
15.0
7.
Elevate all storage at least 15" off floor to facilitate cleaning-storage room 127 and room 114. Storage should be relocated from classroom bathrooms to avoid possible contamination.
10.0
8.
Two flickering lights in gym should be fixed as soon as possible. Replace blown interior and exterior lights on trailer 3. Replace blown lighting where needed. Ventilation ducts to be cleaned in the following rooms: 1st grade Boy's hall bath, girl's bath same hall, media center, room 124-vents in secondary room, room 119 bathroom.
20.0
11.
Store chemicals in locked cabinet or stored at least 5' off floor. The following items found not secured: Aerosols/paints Room 103, Aerosols Room 119, rubbing alcohol & pinesol Room 209, commercial paints under sink Room 202, vomit absorbant Room 105A, Lysol & Febreeze spray in low cabinet Room 103A. Recommend children stain wood outside (during better weather). - They are using multiple cans of stain in Room 102. Teacher is supervising activity.
30.0
General Comments
Drinking Fountains: Clean arch (interior) of mouthpieces. Solid Waste Disposal: Replace lid on sink filter in Art room 124.
Location: 1018 E DAVIE ST RALEIGH, NC 27601-1624 Facility Type: Schools Inspection Date: 01/23/2012
Score: 83
#
Comments
Points
4.
Repair nonfunctional urinal in third grade floor hall boys bathroom. Repair nonfunctional commode in top floor boys hall bathroom in original main building. Repair loose toilet seats in girls and boys hall bathroom in original main building top floor hall bathrooms. Replace permanently stained floor tile in classroom bathrooms. Ex: Floors at base of commodes.
35.0
5.
Clean classroom handwash sinks on 100 hall. Some mold and mildew growth was present in some class sinks.
15.0
6.
Areas of peeling paint are present in original building on classroom walls, original door frames at main entrance, Stairway door frames, classroom door frames, and on original woodwork at main entrance. Keep children away from areas of peeling paint on original wooden door, window, and wall base board components in main building due to the possiblity of exposed areas of lead based paint. Children in classes in the original main building should wash their hands frequently to avoid possible contact with lead dust especially before snacks and meals. Repair ceiling/roof leaks in gym offices, storage rooms, and bathrooms. Roof for this area should be renovated to allow standing water to drain off roof top. Water damaged roof, insulation, and ceiling components in this area should be replaced Repair of leaks in this area is needed A.S.A.P. to prevent mold growth on interior surfaces inside the gym building.
30.0
7.
Class bathrooms can not be used for storage spaces. Ex: Band room bathroom floor being used to store musical instruments, Special needs class bathrooms being used to store equipment like refrigerators, and class bathrooms throughout the building being used to store class supplies or items like carpet squares and furniture.
20.0
8.
Mold buildup was present at bathroom ceiling vents in band modular building. Have vent covers in this area cleaned and have system checked to repair areas of leaks and condensation that could cause mold growth. Duct work for the air conditioning system in this building should be checked to verify that mold growth is not present. Clean duct work if mold growth is present. If cleanup work is required it should be completed when the building is not in use by children or staff. Repair nonfunctional air conditioning ceiling units in classrooms like room # 204. Buildup and residue was present on ceiling tile by vents in media center. Verify that filters for air conditioning system ventilation is being changed regularly. Duct work in this area should also be checked for buildup and residue.
40.0
11.
Cleaning chemicals, aerosol spray cans, chemical surface wipes, rubber cement, and white board cleaner were stored in areas accessible to students in classrooms throughout the campus buildings. These chemical products should be stored in areas that are not accessible to students. Ex: In closed or locked cabinets, closets, drawers, or stock rooms that only staff can access.
Location: 1018 E DAVIE ST RALEIGH, NC 27601-1624 Facility Type: Schools Inspection Date: 07/28/2009
Score: 91
#
Comments
Points
3.
the fountain outside room 110 is running constantly
20.0
4.
the ceilings in all bathrooms need to be washable ( vinyl coated ceiling tiles ); paint is peeling around the window in the downstairs and upstairs girls rooms ( main building ); the boys room next to 101 has moisture damage to the walls around the windows, and the upstairs boys room has heavy damage to the walls behind the commodes; in this bathroom, the floor drain cover is missing, too; repair commode in 104A
15.0
6.
mold spot on the ceiling in the hallway outside room 101A; paint is flaking off the walls in many rooms ( for example 109,102,106,212 ); hallway areas and staircases also show varying degrees of paint damage; room B06 has moisture penetrating the walls from the outside; remove rust stains on closet floor in B02; paint is flaking off ducts and ceiling in the right back corner of the stage; paint is flaking in the skylight outside room 118; several of the gym ceilng tiles are bowed suggesting moisture damage; replace cracked and missing floor tiles; many door frames of doors leading to the outside have some corrosion at the base of the door frame; repair damaged carpet in 206 and re-attach base coving outside room 201
15.0
7.
bathrooms cannot be used for storage ( for example 112A,118,117,123,135,R202-04 ); bathrooms 128A and 128B are used as closets; the toilet in 128A has run dry releasing sewer odors as well as roaches ( roach ran into the toilet ); remove all the storage and keep the bathrooms clean and in working order; in the custodian closet in the gym, the faucet is running constantly
20.0
8.
the windows and window sills still need to be cleaned; paint is chipping off the older single pane windows ( both inside ad outside ); at least 4 windows in the gym are cracked; window in 136 is shattered; trailer 2 has a broken window; in the media center, the ceiling tiles around vents have accumulated a lot of dust
Location: 1018 E DAVIE ST RALEIGH, NC 27601-1624 Facility Type: Schools Inspection Date: 02/25/2008
Score: 92
#
Comments
Points
3.
three fountains near room 131 are corroding and need to be repaired or replaced; rusty, sharp edge are exposed
20.0
4.
the ceilings in all bathrooms need to be washable ( vinyl coated ceiling tiles ); paint is peeling around the window in the upstairs girls room; replace gym bathroom door; the toilet in trailer 3 is running constantly
15.0
6.
paint is peeling off the walls and the ceilings in several areas ( staircase ceiling; stage ceiling; around skylight outside room 105; several upstairs classrooms ); the gym ceiling needs repair ( one tile is completely distroyed due to a leak, another tile in the center of the gym ceiling has heavy damage, and paint is peeling off the ceiling ); paint peeling off closet doors in 201; the carpet is worn and has torn and stained areas; close off a hole in the upper part of the wall in B06; replace missing plastic cover on one step leading to the stage; replace cracked and missing floor tiles; in the media center, the ceiling tiles around the vents have dust build-up; many door frames of doors leading to the outside have some corrosion at the base of the door frame
15.0
7.
do not use bathrooms as storage spaces ( contamination risk ); keep storage in room 127 on racks or otherwise off the floor and clean the floor
10.0
8.
clean the ducts in the gym; replace missing light shield in gym bathroom; the light fixtures in B06 and the light fixtures in the classrooms on the upper floor have debris on the inside; ceiling vent covers in trailer 3 are rusty; paint is peeling off the duct work in the gym
20.0
General Comments
GC # 11 : please remind teachers not to store chemicals including Chlorox wipes in bottom cabinets; store chemicals in locked cabinets or in a cabinet at least 5 feet off the ground
Location: 1018 E DAVIE ST RALEIGH, NC 27601-1624 Facility Type: Schools Inspection Date: 08/22/2006
Score: 89
#
Comments
Points
3.
adjust fountain near 120, and repair and adjust fountain near 110
20.0
4.
all bathroom ceilings need to be washable ( no acoustic tile ); replace bathroom door in gym bathroom; caulk around door in 112 A; major damage to walls behind commodes in boy`s room near 201; walls in large bathrooms need repair and paint ( paint and plaster are peeling )
30.0
6.
carpet is worn and stained in many areas ( some torn areas ); replace transition strip in 104; replace stained ceiling tiles; moldy ceiling tiles in 103, 107, hallway near 217; replace cracked floor tiles; replace missing baseboards; walls in hallways show damage ( from tape being pulled off the wall ); ceilings in staircase are peeling; repair ceiling in B06; repair wall behind fountain near 101
30.0
7.
remove storage out of bathrooms and keep all storage off the floor on racks or pallets ( 128 A and B full of storage )
10.0
8.
parts of the building do not have air conditioning; high humidity in trailers leading to rusty vents and bowed ceiling tiles; clean dust off ducts in gym; shield light fixtures in gym bathroom, 119, 120; clean A/C unit in 103 A; many of the window in rooms with an "A" need to be cleaned; numerous light fixtures have debris in them; burnt light shield in trailer 3 and no light in bathroom in trailer 4; dust the ceiling vents and area around vents in library; remove spider webs off windows ( inside and outside )
20.0
General Comments
Note : clean refrigerator in 128 and provide it with a thermometer; temperature inside refrigerator needs to be below 45 degrees; please remind teachers to store ALL chemicals out of reach of the children ( not under the sink as in 105 A and 207 ); repair toilet seat in 112 A