Facility



Cary Sr. High School


638 WALNUT ST
CARY, NC 27511-4224

Facility Type: Schools
 

Related Reports

Cary Sr. High School
Location: 638 WALNUT ST CARY, NC 27511-4224
Facility Type: Schools
Inspection Date: 08/31/2023
Score: 89.5

#  Comments Points
3. Repair nonfunctional drinking fountains in the following school locations: in the hallway at room #1022, (one fountain), in the gym across from the entrance to the boy`s class locker room #3011, (two fountains), and in the gym lobby beside the entrance to the girl`s bathroom #3127, (two fountains). 20.0
4. Repair the sources of ceiling leaks in the following school bathrooms: girl`s bathroom #2333, boy`s bathroom #2204, and in the girl`s bathroom #2202. Repair and repaint water damaged ceiling surfaces in these bathrooms after the ceiling leaks have been fixed. Repair ceiling leaks and seal hole in the water damaged ceiling of the girl`s locker bathroom #3012. Repair one nonfunctional toilet in the boy`s bathroom at the media center #1030. Repair one nonfunctional toilet in the boy`s bathroom in the 300 building by room #308. Repair partially clogged and poorly draining toilet in the staff bathroom across from science lab stockroom #1009. Repair third in row nonfunctional toilet in the girl`s bathroom #2129. Repair toilets that are leaking on the plumbing pipework in the following school locations: in staff bathroom #2122, in the 1st toilet stall and 3rd toilet stall from the end in girl`s bathroom #2333, and in the end toilet stall of the girl`s bathroom # 2331. Repair major leak on toilet in the 3rd stall on the right in the girl`s bathroom #3127 in the gym lobby. Water is spraying out of cracks on the toilet bowl rim whenever this toilet is flushed. Repair nonfunctional toilet in the 2nd stall on the left that is also in the girl`s bathroom #3127. Repair leaking toilet that also has poor water flow for flushing in the staff bathroom in room #407. Repair partially clogged toilet in the first stall in boy`s bathroom #2231. Repair nonfunctional toilet in the next to last stall of girl`s bathroom #2202 Repair toilet that has poor water flow for flushing in the third stall that is also in girl`s bathroom #2202. Repair nonfunctional toilet in the 2nd stall of girl`s bathroom #2302. Repair toilet that has poor water flow for flushing in the 2nd stall of the girl`s bathroom #2331. Repair toilet that is nonfunctional in the bathroom of the gym boy`s class locker room #3011. Repair nonfunctional waterless urinal in boy`s bathroom #2329. This waterless urinal is also missing a drain filter. Repair partially clogged and slow draining toilet in the 4th stall of the auditorium lobby girl`s bathroom #3102. 35.0
5. Repair two nonfunctional handwash sink faucets in the girl`s bathroom #2102. Repair one handwash sink faucet that has poor water flow for washing in the boy`s bathroom in the #200 building across from the cafeteria. 15.0
6. Repair active roof and ceiling leaks in the following school locations: in the science lab class stock room #1009, in the hallway at the entrance to the construction technologies classroom #2111, in room #1023, in room #1015, in room #1107, in the cafeteria dining room in the 200 building, in the teacher`s lounge room #2301, in the hallway at room #2324, in the teacher`s lounge room #3123, and in the hallway at room #3132. Replace water-stained ceiling tiles in these locations after the sources of the leaks have been fixed. Replace water-stained ceiling tiles in the media center main room #1030 and in the hallway at the entrance to the boy`s bathroom across from the media center. Roofing repairs to address these leaks have already taken place in this building. Repair damaged ceiling at the entry into the gym girls' team locker room #3143. There are holes present in the ceiling in this location. The holes should be sealed. If the damage to the ceiling in this location is caused by leaks the source of these leaks should be repaired. 15.0
8. Replace broken ceiling light shield cover in the instructional kitchen #2105. Replace one missing ceiling light shield in the girl`s bathroom #2331 and three missing ceiling light shields in the boy`s locker room #3011. Repair nonfunctional vent hood in the chemistry lab classroom #1008. 20.0
General Comments
Replace broken bench seat in girl's locker room #3012 or remove the exposed bench support posts. These exposed bench posts could pose a trip and fall hazard and cause other possible injuries.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Cary Sr. High School
Location: 638 WALNUT ST CARY, NC 27511-4224
Facility Type: Schools
Inspection Date: 10/26/2020
Score: 90

#  Comments Points
3. Repair nonfunctional drinking fountain in hall by classroom 1025. 20.0
4. Repair nonfunctional toilets in the girls hall bathroom by the media center,(one toilet), in the girls bathroom #2233, (two toilets), in the boys bathroom in building #300, (one toilet), in the gym boys bathroom #3129, (one toilet), in the girls locker room bathroom #3143 (one toilet), and in staff bathroom #3147, (one toilet). Repair leaking toilets in girls bathroom #2233, (one toilet), and in the varsity boys fieldhouse locker room bathroom, (one toilet). Repair broken latch on toilet stall door in the gym boys locker room bathroom #3011. Repair clogged floor drain in the varsity boys fieldhouse locker room bathroom/showers. 20.0
5. Repair hand wash sink faucets that have loose operation valve handles in the Boys hall bathrooms #2104 and #2231. Repair nonfunctional hand wash sinks in the boys bathroom #2304 and in the boys bathroom in the 300 building. 15.0
6. Repair ceiling leaks in the hall by room #1023, in the media center, in the building # 10 entry hall by the media center, in the hall by girls bathroom #2302, in the cafeteria dining room in building #200, in the hall by custodial closet #2336, in the gym hall by the concession stand #3135, in the hall by the girls locker room #3143, in the hallway by the band and chorus rooms, in the gym weight room #3146, in the girls locker room/bathroom #3012 over the toilets,(major water damage to the ceiling), and in the boys locker room #3011, (leak is in the light fixture). Repair peeling ceiling paint in the fieldhouse varsity boys locker room. Clean top ledges of the upper wall support beams in the auxiliary gym of trash and dust residue. All of the covered sidewalk/walkway interior ceilings are rusted and have peeling paint. Repair or replacement of the walk way roofs are needed to prevent increased deterioration. (Example: The walkway roof between the 300 and the 400 buildings). Replace bent metal wall plate that covers the plumbing access point in the rear toilet stall of the boys hall bathroom at the media center. The sharp edges of this plate could create a possible cutting hazard. Please repair A.S.A.P. 15.0
8. Repair/ close loose and hanging ceiling light shields in the band room #3121 and in the choral room #3120. (Safety hazard) Repair A.S.A.P. 20.0
11. Fire ant colonies are present along the field house foundation and on the back of the 400 building near the entrance and sidewalk. Pest control treatments are needed to remove the fire ants. (Safety hazard) 10.0
General Comments
Replace missing shower head in the boys locker room #3011 showers. School Facility Sanitation Inspection Completed.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Cary Sr. High School
Location: 638 WALNUT ST CARY, NC 27511-4224
Facility Type: Schools
Inspection Date: 02/18/2019
Score: 90

#  Comments Points
3. Repair missing front panel bar on drinking fountain in gym lobby by restroom # 3129. Reattach loose drinking fountain to wall in building 1000 hall. 20.0
4. Repair peeling ceiling cover in boys bathroom # 2204. Replace missing floor tiles in girls locker room bathroom. Replace loose and water damaged floor tiles in office staff bathrooms and in health room bathroom. (#1104K, #1100E, #1104D) Repair leaks at the base of the toilets in these same office staff and health room bathroom. Repair missing and loose toilet seats in boys and girls locker room bathrooms and in boys bathroom # 3129. Repair nonfunctional toilets and urinals in girls bathroom # 3102, boys bathroom # 3129, boys bathroom #2231, and in girls bathroom on first floor in back of 2000 building. Repair leaking toilet handle pipe in 1000 building boys bathroom. Repair loose toilet fixture in girls bathroom # 3102. 50.0
5. Repair nonfunctional hand wash sink in boys bathroom # 2204 and in teacher lounge # 2301. 15.0
6. Repair ceiling and roof leaks in the 1100 hall, in the auditorium lobby, in room # 1009, and in the hallway by the ROTC office # 300B. Replace chipped and broken floor tile in the auditorium lobby. 15.0
General Comments
Custodial staff has done a good job at keeping the buildings, hallways, restrooms and locker rooms clean.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Cary Sr. High School
Location: 638 WALNUT ST CARY, NC 27511-4224
Facility Type: Schools
Inspection Date: 06/05/2017
Score: 96.5

#  Comments Points
4. Toilet Seat in women's restroom (administration building) is not properly attached. 0.0
5. NO Paper Towels available in women's locker room. There is only one towel dispenser and it is broken. Replacement needed. Consider adding a second dispenser. . . Men's Sink Faucets are leaking in the toilet room of the 300 building. 20.0
11. There is a lot of pooled water on the ground. Many puddles. . . Breeze Way ROOF is actively leaking in areas with chipped paint, moss and mold accumulated. Active dripping from overhead outside / at entrance to the 300 building and 1100 building. 15.0
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Cary Sr. High School
Location: 638 WALNUT ST CARY, NC 27511-4224
Facility Type: Schools
Inspection Date: 07/10/2014
Score: 91

#  Comments Points
6. Replace the broken mirror in the dance room. The older carpet in classrooms ( like 1106 )and teacher room in 3000 building are stained. There is moisture damage to the wall in 410, and the carpet is stained. The outside doors to the 400 building have corrosion damage. There is moisture damage to the wall under the AC unit in 302. The metal walkway cover between 200 and 300 building is very rusty, and paint is coming off in large flakes. The metal walkway cover behind the cafeteria is also rusty and has flaking paint. The black paint above the windows on the outside of buildings 300 and 400 is peeling off. 15.0
7. The bottom shelf of many storage shelves in custodian rooms and classroom storage areas ( see art room ) are too close to the floor. Wax and dust/debris are building up under the shelves. Raise the bottom shelves to a level where you can clean under the shelves. 10.0
8. The windows in 300, 400, and especially 600 building are in very bad shape and need to be replaced. The window frames are mildewy and rusty, and the paint is flaking off. Some of the windows do not close ( leaving the air conditioning to fight an uphill battle against moisture in the rooms ). The caulking around the windows is mildew and sometimes ineffective due to shrinking and cracking. The windows in 601 seem to be in the poorest condition. The higher structures in the gym are dusty. Clean walls and windows in the staircase in 2000 building. Clean the window tracks and blinds ( spider webs ). 40.0
9. Repair a hole in the ceiling in the womens class locker room, and clean up the remaining water on the floor in that locker room. Clean the ceilings and ceiling vent covers in the locker rooms as needed. 15.0
11. There are a lot of dead insects in the 400 building. I also saw two live roaches hiding under the lockers in 400 and at the entrance to 300 building. 10.0
General Comments
Note : The light green weight benches should be replaced. The covers for the cushions are completely torn making them impossible to clean ( allowing viruses and organisms like MRSA to thrive on the benches ).
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Cary Sr. High School
Location: 638 WALNUT ST CARY, NC 27511-4224
Facility Type: Schools
Inspection Date: 05/15/2013
Score: 89

#  Comments Points
3. Some of the water fountains do not have enough pressure. Most can be adjusted. The water should come in contact with the mouth guard when the button is fully pressed. 20.0
4. (A)There is a lot of graffiti on rest room walls and on stalls. (B)There is a water leak at a toilet in boys rest room 2231. There seems to be a lot of bad odor around many of the waterless urinals. (C) One rest room has paint splattered all over the tile floor. This makes it difficult to tell if it is clean or not. 50.0
7. Clean under wire shelving units in janitor closets where needed. Shelving should be high enough so you can sweep and mop under the shelves or the bottom needs to be boxed in so nothing gets under the bottom shelf. The minimum hight for shelving is 15 inches but if it is clean and you can sweep and mop etc that is good enough. 20.0
8. There was one air conditioner in a class room that has been taken apart with exposed insulation. It needs to be repaired and put back together. 0.0
9. Replace missing or damaged shower heads. You may want to install vandal resistant shower heads that are not likely to be removed. 20.0
General Comments
There is a lot of dust build up on top surfaces of pipes and ducts etc in the gym.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Cary Sr. High School
Location: 638 WALNUT ST CARY, NC 27511-4224
Facility Type: Schools
Inspection Date: 10/01/2010
Score: 91.5

#  Comments Points
3. Water fountains need better cleaning in 1100, 1000, 200, 300 bldgs. 20.0
4. Bathroom baseboards need better cleaning in 1100, 1000, 200, 400, & gym. Clean bathroom walls in 1000, 200. 15.0
7. Janitor`s closets need better cleaning, esp. 300, 400, 3000, gym downstairs, & #2312. Storage should be kept off the floor in janitor`s closets, special educ. bathrooms & Food Lab in 2000 bldg. Opened bags of flour were stored with cleaner & shortening was stored on the floor in Food Lab in 2000 Bldg. Bottom shelves of racks in janitor`s closets should be raised off the floor to allow access for mop or broom to clean. 20.0
8. Vents and blinds dusty esp. 1100, 200, 300, 400, gym, 3000 & 2000 bldgs. 20.0
9. Tops of lockers need dusting in locker rooms. 10.0
General Comments
Room #3122 Band/Lib. Workroom needs cleaning. Ledges, ducts, etc. very dusty in aux. gym. Repair leaking janitor's sink in 200 bldg.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Cary Sr. High School
Location: 638 WALNUT ST CARY, NC 27511-4224
Facility Type: Schools
Inspection Date: 01/22/2007
Score: 92.5

#  Comments Points
4. Repair nonfunctional toilets in girls restrooms in buildings #10 and #11. Repair clogged commode in girl`s locker room. 20.0
6. Repair ceiling leaks in facility classrooms and storage areas. Replace water damaged ceiling tile after sources of leaks are corrected. Ex: Science rooms and store rooms in buildings #10, #11, and in modular building for special needs children. 15.0
8. Clean ducts and replace filters on ventilation system in buildings. Dust is being blown through vents and onto surounding ceilings. Ex: Media center and in regular classrooms. Replace nonfunctional lights and ballasts in gym locker rooms. Repair leaks on piping for class and hall H.V.A.C. systems in buildings. Example: Buildings #7 and #2. Exterior insulation on pipes has mold growth. Insulation with mold growth on pipes should be removed and replaced. 40.0
General Comments
All chemical products that are flammable, caustic, or hazardous should be stored in areas out of reach of students when instructors are out of classrooms. Ex: Hydrochloric acid was left in one science classroom vent hood unattended. Note: No children were on campus at time of inspection due to teacher workday.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Cary Sr. High School
Location: 638 WALNUT ST CARY, NC 27511-4224
Facility Type: Schools
Inspection Date: 04/15/2004
Score: 95

#  Comments Points
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Cary Sr. High School
Location: 638 WALNUT ST CARY, NC 27511-4224
Facility Type: Schools
Inspection Date: 09/12/2001
Score: 95.5

#  Comments Points
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Cary Sr. High School
Location: 638 WALNUT ST CARY, NC 27511-4224
Facility Type: Schools
Inspection Date: 02/16/1998
Score: 0

#  Comments Points