Repair ceiling leak and replace water damaged ceiling tile in class bathroom #510A. Replace missing wall base tile by doorway in class bathroom #510B. Repair ceiling leak and replace water-stained ceiling tile in class bathroom #506B. Repair clogged toilet in class bathroom #605A. Repair toilet that is leaking on the plumbing pipework in class bathroom #605B. Repair two toilets in the girl`s bathroom #601E and two toilets in the girl`s main hall bathroom adjacent to the office. All four of these toilets are leaking either on the plumbing pipework or on the flush valves. Repair two nonfunctional urinals in the boy`s hall bathroom #109A.
35.0
5.
Repair countertop sink drains that are clogged in classroom #510 and classroom #607.
15.0
6.
Repair roof and ceiling leaks in the following school locations: in classroom #605, in classroom #604, in the hallway outside of room #602, and in the hallway entrance of the 400 building at the art classroom #400A. Repair the causes of these leaks. Replace water damaged ceiling tiles in these locations after the leaks have been fixed. Replace loose, sagging, and uneven floorboards on entry ramps for class trailers #2, #3, and #4. Priority repairs for safety are needed to prevent trip and fall hazards.
15.0
7.
Classroom supplies and student clothing were stored in classroom bathroom #607A. Only items related to bathroom use should be kept in class bathrooms. Bathrooms are not clean storage locations. The storage of these class items and clothing in class bathrooms can become a means of transfer for communicable disease pathogens including stomach flu. The storage in this class bathroom is also an impediment to the cleaning and repair of this restroom facility. Please remove. Repeat inspection demerit item for this same class bathroom.
20.0
8.
Multiple ceiling lights were nonfunctional in the following school locations: in the gym, in the cafeteria dining room, in the entry to the media center, in the main office lobby, in the main office health room #100B, in classroom #509, in classroom #603, in classroom #604, in classroom #605, and in classroom # 607. Nonfunctional lighting is a major problem throughout the entire school and requires priority repair. Replace burned out ceiling light over the toilet stalls in boy`s bathroom #401A. Dust buildup is present on top of the ceiling ventilation ductwork in the cafeteria. This ductwork requires cleaning.
Repair toilets that have poor water flow for flushing in the first stall in girls hall bathroom #401B, in the second stall of boys bathroom #401A, in the end stall of boys bathroom #601E, in the staff hall bathroom #609, and in classroom bathroom #508A.
20.0
5.
Repair two nonfunctional hand wash sinks at the the entrance to girls bathroom #109B. Repair hand wash sink with a leak on the base of the faucet also at the entry to girls hall bathroom #109B. Repair clogged hand wash sink drains in classrooms #509 and #510.
15.0
6.
Replace missing ceiling panel at light fixture in room #600. Repair ceiling leaks at light fixtures in classrooms #605 and #607. Ceiling leaks are also present in classroom #603, class bathroom #510A, and in hall staff bathroom #609. Repair the sources of these roof and ceiling leaks. Replace water stained ceiling tiles in these areas after the leaks are fixed. The carpeting in the media center main room #203 is permanently stained and frayed and is in need of replacement. Repaint chipping and peeling walls in class bathroom #505A. Replace broken and buckled floor tile at the bathroom entry in classroom #504. Priority repair is needed to prevent potential trip and fall hazard. Repair torn ground padding at the front of the slide on the Pre-K playground. Safety repair is needed to prevent possible trip hazards. Plumbing leak in the wall behind toilet in boys bathroom #109 requires repair. The wall plate where this leak is located should be replaced after repairs are completed.
15.0
7.
Classroom supplies were stored in classroom bathroom #607A. Only items related to bathroom use should be kept in class bathrooms. Bathrooms are not clean storage locations for items used in classrooms. The storage of these items in a class bathroom is also an impediment to the cleaning and repair of these facilities. Please remove.
10.0
8.
Repair six nonfunctional ceiling lights in the gym. Reattach one loose ceiling light shield cover in the gym. Replace one missing ceiling light shield cover in the cafeteria dining room #300
20.0
General Comments
Repair loose left hand rail on steps of the new playground structure. (Maximo # 72843-10400) Priority repair for safety is needed. Annual school facility sanitation inspection completed.
Repair toilet that is leaking around the base in boys hall bathroom #109A. Repair nonfunctional toilet in the first stall of girls hall bathroom #109B.
20.0
5.
Repair clogged hand wash sink drain in girls bathroom #200B. Repair clogged sink drain in classroom #603.
15.0
6.
Repair roof and ceiling leaks in the following school locations: in classrooms #504 and #508 above the air conditioning system units, in the hall at the entrance to classroom #602, in classroom #402, in classroom #605, (Major Leak), in classroom #607, in bathroom #609, (Major Leak), and in the hallway at the entrance to the girls bathroom #401B, (Major Leak). Repair damaged upper wall area in the art classroom #400. Repair chipped wall paint in classroom bathroom #508A.
15.0
8.
Clean dust build up from the top of the ceiling duct work in the cafeteria dining room #300. Ceiling vents have dust residue in the gym, (room #700), and require cleaning. Multiple ceiling light ballasts are nonfunctional in hallways, classrooms, bathrooms, and offices throughout the entire school facility. Lighting repair is required.
20.0
11.
Live cockroach was present in the front lobby hall at the main office. Continued pest control treatments are needed to reduce the pest presence in the school building.
10.0
General Comments
Replace broken toilet tissue dispensers in bathroom stalls in boys bathroom #601D and in girls bathroom #109B. Potentially harmful chemical products including aerosol spray cans were left in areas accessible to students in classroom #605 and in the art class room #400. Chemical products and aerosol spray cans should be stored in areas only accessible to staff including closed or locked cabinets and closets. Classroom supplies were stored in class bathroom #607A. Class bathrooms are not clean storage locations. The class items stored in this restroom could become a means of transfer for disease pathogens including norovirus and stomach flu. There is also a safety concern that these heavy objects might fall on students using this bathroom. Please remove. Replace missing ceiling light shield cover in classroom #603. Repair loose vent grate on door to restroom in classroom #510.
Repair loose water fountain nozzle in classroom #510.
20.0
4.
Repair nonfunctional toilets in the girls hall bathroom #109B and in the classroom bathrooms #503A and #506A.
20.0
5.
Repair nonfunctional hand wash sinks in the boys hall bathroom #109 and in classroom #607. Classroom #607 hands sink has low water pressure. Repair clogged hand wash sink in classroom #509. Repair leaking hand sink faucets in classrooms #503 and #505.
15.0
6.
Repair ceiling and roof leaks in the 600 hall. Major ceiling leaks are present in the 600 hall at bathroom #609. The drop ceiling tiles have collapsed in this location as a result of the leaks. Ceiling leaks are also present in classroom # 605 and in bathroom #609. Repair ceiling leak at air conditioning unit in classroom #508. Repair ceiling and roof leaks in the cafeteria dining room. Replace water damaged ceiling tiles after the ceiling leaks are repaired. Replace cracked and damaged floor tiles in the media center office #203.
15.0
8.
Repair nonfunctional ceiling light in student boys bathroom #200A.
20.0
11.
Cockroach was present in boys bathroom #401A. Recommend professional pest control treatments in facility.
Repair nonfunctional toilets in staff bathrooms #204 A, girls hall bathroom # 601 E,(second stall), media center staff bathroom #203 G, and in the gym building #700 girls bathroom. All of these toilet fixtures have poor water flow. Repair leaking toilet in girls hall bathroom # 200B. (First stall) Repair ceiling leaks in health room bathroom #100 B, in student hall bathroom #609, and in classroom bathroom #510 A. Replace water damaged ceiling tiles after these leaks are fixed. Repair loose base stripping on toilet stall divider wall in boys hall bathroom #109A.
35.0
6.
Ceilings and roof leaks remain a major problem in campus buildings. Repair ceiling leaks in the cafeteria dining room #300 at vents, (Mold growth present in these leaks), in the 600 hallway, in the 500 hallway, in classroom #503, in classroom # 508, in classroom #602, in classroom #604, and in classroom #605. Replace water damaged ceiling tiles after repair of these leaks.
15.0
7.
Class supplies are stored in classroom bathroom #607A Bathrooms are not clean storage locations. Only toilet and diapering supplies should be present in class bathrooms.
10.0
8.
Repair nonfunctional ceiling light ballast in the 600 hallway outside of room # 602.
20.0
General Comments
Repair broken swing support beam on stand alone outside playground structure by fence at tree line and baseball field first base line.
Repair nonfunctional commode in boys hall restroom # 401 A. Adjust urinal water flow in boys restroom # 109 A. Water is overflowing urinal basin.
20.0
5.
Repair clogged hand wash sink drain in classroom # 112.
15.0
6.
Ceiling and roof leaks are a major problem in buildings on campus. Ceiling leaks are severe in the 600 building. The following areas were observed to have ceiling leaks: 600 hall(severe actively dripping leaks), room 604 (severe leak with stained moldy ceiling tile), room 605, staff bathroom # 609, second grade building room# 402, room # 114, and room # 113. Sources of the ceiling leaks should be repaired and water/mold damaged ceiling tile replaced. The carpet in room # 605 is wet from the ceiling leaks. The water stained and drenched carpet in this room should be replaced after leaks are repaired.
30.0
8.
Ceiling lights throughout the buildings are non functional. Light ballasts require repair or replacement in the following locations: 200 hall, 100 hall, music room, cafeteria dining room, gym/multipurpose room, 400 building, 600 building, handicap bathroom # 107, bathroom lights in rooms # 601 D and # 601 E, and in boys hall bathroom # 200 A. Repair nonfunctioning light switch on 200 hall by teachers lounge.
20.0
General Comments
Recommend notice to teachers that no class supplies or file cabinets should be kept in class bathrooms. Storage of these items in class restrooms are an impediment to cleaning. Recommend sending a notice to teaching staff that all cleaning chemicals and aerosol spray cans can not be stored in areas accessible to students in classrooms. These chemical products should be stored in locations like locked cabinets or in teacher desk drawers.
Repair water fountain outside of 200A (on right), rusting nozzle and blistering on case around push bar. Adjust water pressure on water fountain across from 407 so that students can drink from it without mouth contact.
20.0
4.
Repair walls behind toiles in bathrooms 23, 503, 609, 511A, 109A and 507. Repair baseboard tile in 200B. Repair rusting divider in 401B. Repair peeling ceiling and wall pain in 401A. Repair urinal in 401A.
15.0
6.
Repair wall in room 111 at window. Small water stains on ceiling tile in 105 and in hall at the 109 intersection, check for current leaks.
0.0
7.
All storage must be 15 inches above the floor and arranged to allow for easy cleaning. Storage rooms in art and gym and a couple of storage closets need rearranging.
10.0
8.
Ceiling vents in gym are very dusty.
0.0
11.
All chemicals/cleaners that are labeled 'keep out of reach of children' must be at least 5 feet up or behind a teacher's desk.
Note : The fountain near 609 is turned off or not working. Clean the fountain in 509.
0.0
4.
Paint the walls behind the urinals or commodes in 401 A, 504 A, 510 A, and 508.
The ceiling tiles in the bathrooms in the 600 building are acoustic tiles. They should be replaced with vinyl coated, washable tiles.
15.0
6.
In the 600 building, wooden boards were used to attach mini blinds. The paint on the boards is starting to flake off. One window in the library has a small leak, and mold has formed in a corner near the window.
15.0
8.
Note : The windows and window tracks in the 600 building still need to be cleaned.
0.0
11.
There are mice in the cabinets under the sinks in 105, 113, and 114.
Please remind all teachers that chemicals including cleaners and Chlorox wipes need to be stored out of reach of children in a top cabinet or a locked cabinet.
Thoroughly clean the cafeteria walls. There are marks from chairs etc. The cafeteria walls may need to be painted.
15.0
7.
The media center/library is dusty and musty. Thoroughly clean high shelving and tops of cabinets. There are buckets of wax stored in one of the exit halls near the cafeteria dinning room. These buckets should be stored in a proper storage room on shelves.
20.0
11.
There is a damaged grate on a storm drain in the courtyard. It needs to be repaired so it is not a trip hazard. ... There are seven pallets behind the dumpster and three pallets at the back dock. Get rid of the pallets and old chairs etc out by the dock.
Water fountains in cafeteria dining room and in some kindergarten rooms need to be cleaned.
20.0
6.
The floors & mop basins of many custodial closets need to be thoroughly cleaned. Ceiling tiles missing in various places due to repair work on leaks.
15.0
7.
Storage areas of kindergarten rooms & teacher work rooms need to be organized so that storage is off floor.
10.0
8.
Exhaust fans in staff restrooms and small toilet rooms in classrooms need to be cleaned of dust buildup. Windows 7 blinds in music room are dusty. Window facing cracked in some classrooms.
Repair water fountains with low water pressure. Ex: Fountains in Kindergarten/Pre-K hall. Repair nonfunctional water fountain in 5th grade hall.
20.0
4.
Repaint peeling walls in shared bathrooms between classrooms.
15.0
5.
Repair nonfunctional sink faucet and urinal in boys bathroom in 5th grade building.
15.0
6.
Repair ceiling leaks in 600 building. Ex: Room 605 and hallway. Repair ceiling leak in health room bathroom.
15.0
7.
Do not store items like cups or toys in Pre-K class bathroom. Only items related to diapering should be in bathroom.
10.0
8.
Clean ceiling vents in computer lab, gym, cafeteria, class bathrooms, and in classrooms on third/fourth grade hall. Clean H.V.A.C. unit vents in all classes. Change filters for ceiling vents in gym.
20.0
11.
Cleaning chemicals, aerosol cans, and chemical surface wipes should be stored in areas not accessible to children. Ex: In cabinets. Cleaning chemical products were found in classes throughout facility in areas accessible to children.
30.0
General Comments
Emergency clothing items for children in health room bathroom should be stored in sealed containers. Items not related to bathroom use should not be stored in this bathroom. Replace missing toilet tissue dispenser in girls bathroom in gym.