Interim Temporary School Location Site
Location: 2600 TIMBER DR GARNER, NC 27529
Facility Type: Schools
Inspection Date: 02/13/2024
Score: 90

#  Comments Points
4. Repair damaged floor covering and wall covering at urinals in boy's bathroom #M-209 in mobile unit #2. Repair toilet that has poor water flow for flushing also in boy's bathroom #M-209. Seal hole in wall in boy's bathroom #M3-7 in mobile unit #3. 50.0
5. Repair disconnected drain pipe on the sink by the washing machine and dryer in the laundry room of the home economics classroom that has been converted to a teachers lounge in the main building. This room is located across the hall from the cafeteria. 15.0
6. Repair the source of the roof leak in the media center over the rear wall windows. Repair water damaged wall covering and window framework beneath the roof leak location after the source of the leak has been fixed. Replace missing ceiling tiles and repair damaged drop ceiling grid as part of the leak repair work. 15.0
8. Repair nonfunctional vent fan motor for kiln in the art classroom #102B. Replace missing ceiling vent fan covering in the girl's bathroom #M2-12 in mobile unit #2. Priority repairs for safety are needed due to the exposed vent fan blades. Repair nonfunctional ceiling light in staff bathroom #M3-11 in mobile unit #3. 20.0
General Comments
Repair or replace broken ground anchoring cable on the mesh cable climbing tube on the playground structure closest to the main building.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Interim Temporary School Location Site
Location: 2600 TIMBER DR GARNER, NC 27529
Facility Type: Schools
Inspection Date: 01/13/2022
Score: 92.5

#  Comments Points
3. Repair nonfunctional drinking fountain in modular building #3. 20.0
4. Repair clogged toilet in the men`s locker room bathroom #111A. Repair leaking toilet at water pipe on top rim in staff bathroom # 112B. Repair nonfunctional toilet in girls bathroom # M2-12. Repair toilet that has poor water flow in girls bathroom #M1-12. Repair nonfunctional urinal in boys bathroom #M2-09. Repair nonfunctional urinal in boys bathroom #122. 20.0
6. Repair ceiling leak in the media center. (Room #113) Replace water stained ceiling tile and repair water damaged wall paint beneath the ceiling leak and at the window in the media center. Repair ceiling/roof leak in cafeteria dining room #116. Replace water stained ceiling tiles in cafeteria after the leak is fixed. Replace damaged floor board on rear entrance ramp on modular building #1. There is a hole in this ramp floor board that could create a trip and fall hazard. Priority safety repair is required on this ramp. Repair and seal hole in wall of girls bathroom #M3-10. Repair torn wall paper in boys bathroom #M3-07. Replace broken door window glass on entrance door to the main corridor at the cafeteria. 15.0
8. Repair nonfunctional heating and air conditioning system for classroom #M1-03. Repair nonfunctional ceiling vent fan in staff bathroom #M1-13. Repair nonfunctional ceiling vent fans in girls hall bathroom #M2-12. Clean classroom ceiling vents of dust residue in modular building #1. The filters for the heating and air conditioning systems in the classrooms for modular building #1 may require changing. Repair nonfunctional ceiling light fixtures in the girls locker room #111C. 20.0
General Comments
School facility sanitation inspection completed.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Interim Temporary School Location Site
Location: 2600 TIMBER DR GARNER, NC 27529
Facility Type: Schools
Inspection Date: 10/05/2020
Score: 92.5

#  Comments Points
4. Repair two nonfunctional urinals in the boys main building bathroom #122. 20.0
5. Repair nonfunctional hand wash sinks in the boys locker room bathroom #111A and in girls bathroom #123. Repair loose hand wash sink faucet in boys modular bathroom #M3-07. 15.0
6. Repair ceiling leaks in the media center room #113, in the boys modular building bathroom #M1-9, in the staff bathroom #M1-13, and in the girls modular bathroom #M3-10. Replace stained and damaged ceiling tiles in the girls modular bathroom #M1-12, in staff bathroom #M1-13 and in the boys Modular bathroom #M1-9. Mold growth was present on the ceiling leak in the boys modular bathroom #M1-9. This leak requires priority repair. Repair leaks above rear exit door in the media center room #113. Repair and replace water damaged and rotted floor in toilet stall in the girls modular bathroom #M3-10. Repaint ceiling vent in staff bathroom #M2-13. The paint on this vent is peeling. 30.0
7. Remove the stacks of chairs stored in the girls locker room bathroom #111D. Bathrooms are not clean storage locations and the stacks of chairs stored there are an impediment to the cleaning and repair of this restroom facility. 10.0
General Comments
School Facility Sanitation Inspection Completed.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Interim Temporary School Location Site
Location: 2600 TIMBER DR GARNER, NC 27529
Facility Type: Schools
Inspection Date: 04/22/2019
Score: 88

#  Comments Points
3. Repair nonfunctional drinking fountain in Modular Building #3. 20.0
4. Visible mold growth and water damage is present around ceiling vents and on adjacent ceiling tiles in Modular building # 1 staff and girls student restrooms. (M1-12 and M1-13) Ceiling/roof leaks are present in Modular Building #1 boys restroom. Ceiling and roof leaks and adjacent mold growth on ceiling vents are present in Modular Building #2 staff bathroom # M2-13. Repair chipping paint on ceiling vents in Modular Building #2 boys restroom # M2-09. Repair torn wall paper in Modular Building # 3 boys and girls bathrooms #M3-10 and M3-07.Modular Building #3 girls bathroom toilet stall floor is severely water damaged and sagging. (M3-10) Repair is needed on this floor area A.S.A.P. to prevent possible collapse. Repair nonfunctional toilets in girls bathroom M1-12 (Modular 1) and in staff bathroom M2-13 (Modular 2) Repair damaged toilet tissue dispenser in boys bathroom M2-09 (Modular 2) 50.0
5. Repair loose hand wash sink faucet in boys bathroom # M3-07. (Modular 3). 15.0
6. Repair hole in hall way wall behind boys bathroom # M3-07 door. (Modular 3) Repair damaged exterior wall skirt on Modular Building # 1 on side adjacent to the playground. 15.0
8. Repair nonfunctional ceiling lights in boys bathroom M3-07. (Modular 3). Replace cracked ceiling light fixture shield in boys hall bathroom # M2-09. (Modular 2) 20.0
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Interim Temporary School Location Site
Location: 2600 TIMBER DR GARNER, NC 27529
Facility Type: Schools
Inspection Date: 02/21/2018
Score: 91

#  Comments Points
4. Repair torn wallpaper and small hole in the wall in boys room M3-07. Clean mildew/mold from the walls and ceilings in M2 and M1 building bathrooms, repair the source of the issue for both buildings. Check for leak at water damaged ceiling tile in M2-12, replace this tile it is caving in. Repair toilet in 123. Repair urinal in 122. 35.0
5. Repair sinks in boys restroom 122, two have been turned off at the valves because the self-metering faucets don`t turn off. 15.0
6. Clean/repaint walls in the gym. Repair torn wallpaper in hall outside of M3-06. Replace missing/loose wall trim in M3-06, M1-01 and as needed in M4 building. Repair water spot in ceiling in room 401 (per AP this is new, and may indicate a new leak). Repair broken floor tile in room 402. Floor needs cleaning in M1-01 and 103. Dusty wall needs cleaning in 305. 15.0
8. Replace burned out light in M1-12. Replace broken blinds in room 305. 0.0
9. Walls need cleaning/repainting in locker rooms. 15.0
11. Mouse droppings found below sink in room 106. Increase pest control measures. 10.0
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Interim Temporary School Location Site
Location: 2600 TIMBER DR GARNER, NC 27529
Facility Type: Schools
Inspection Date: 01/24/2017
Score: 93.5

#  Comments Points
4. Repair a large hole in the floor next to the entrance to the mens bathroom in the 200 building. The floor tiles in the 400 building boys bathroom are very stained around the urinals. In the 300 building boys bathroom, the flooring was not properly installed along the edge of the flooring sheet, and two corners now need repair. One toilet in the 400 boys bathroom is out of order. One toilet in the girls bathroom in 400 is out of order, and one has a damaged toilet seat. 35.0
5. One of the hand sinks in the womans bathroom in the 200 building has hardly any water pressure. One of the hand sink fixtures in the boys bathroom in the 400 building is very wobbly and needs to be tightened down. In the main building, the hand sinks in both boys and girls bathroom need to be re-caulked. 15.0
6. Repair a large hole in the gym wall. 15.0
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Interim Temporary School Location Site
Location: 2600 TIMBER DR GARNER, NC 27529
Facility Type: Schools
Inspection Date: 06/16/2015
Score: 93.5

#  Comments Points
4. A) Repair the wall behind the sink in the 200 building boys' bathroom. Check for a leak in the staff bathroom ceiling in the 200 building, there is mildew on the ceiling and light fixture shield; also, replace the moisture damaged ceiling tiles. C) The bathroom floors in the 200, 300, and 400 buildings need cleaning and/or to be stripped and resealed. 30.0
5. Repair the toilet with the plastic bag in the girls' bathroom. 15.0
6. Comment: Replace the missing wall panel cover strips in the 400 building hallway. 0.0
8. Clean the exhaust vents in both boys' and girls' locker room bathrooms. Clean the air returns outside of the bathroom in the 300 building. 20.0
General Comments
Repair the damaged crawlspace flashing on the outside of the 300 building.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Interim Temporary School Location Site
Location: 2600 TIMBER DR GARNER, NC 27529
Facility Type: Schools
Inspection Date: 01/08/2014
Score: 100

#  Comments Points
General Comments
CLEAN UP CONSTRUCTION DEBRIS. CLEAN JANITORS CLOSETS IN MODULAR UNITS.