Wake County Plan Review and Recreational Sanitation Section recommends pools be hyper chlorinated at least twice a month. This activity should be accurately logged on the CPO check list form.
Indoor Pool, Flowmeter Actual Flow Rate: 80 GPM
Max Flow Rate of Drain Covers: 560 GPM
0.0
25.
In Pump Room, no ventilation detected. Repair the air flow so that continuous forced ventilation is provided to Pump Room.
In Chemical Room, forced ventilation detected but low. Improve air flow to the chemical room.
In the Chemical room, non-chemical storage observed including tiles, paper towels, and strainer baskets. Chemical rooms are limited to chemical storage only. Remove the non-chemical items.
In the Chemical room observed paper-bag chemicals stored on a low pallet, less than 12-inches off the ground. Move the chemicals up so stored at least 12-inches up off the ground.
2.0
General Comments
Wake County Plan Review and Recreational Sanitation Section recommends pools be hyper chlorinated at least twice a month. This activity should be accurately logged on the CPO check list form.
No night swimming. No CPO signature today due to COVID-19 precautions. Inspection report is emailed to CPO. CPO did not know Pool Volume at time of inspection. CPO will notify REHS of pool volume once calculated. Your REHS is Joanne Rutkofske, 919-623-0459.
Heater not functional, must be functional at permitting in 2022.
0.0
5.
Must have readings 2x/day 6hrs apart 7days a week or show pool closed and close the pool. Need at least 3 National/WCES CPO on staff to provide 7days a week coverage. Must post all CPO certificates in the pump room. This can be a WCES 6pt closure item.
4.0
25.
Must store all chemicals 12inches off the floor. Need a larger chemical room. Switching to liquid cl and pH chemicals. Watch out for empty containers,
2.0
General Comments
Wake County Plan Review and Recreational Sanitation Section recommends pools be hyper chlorinated at least twice a month. This activity should be accurately logged on the CPO check list form.
Must have readings 2x/day 6hrs apart 7days a week. Need at least 3 National/WCES CPO on staff to provide 7days a week coverage. Must post all CPO certificates in the pump room. This can be a WCES 6pt closure item.
4.0
24.
Provide spare filter baskets.
0.0
25.
Must store all chemicals 12inches off the floor.
2.0
29.
Hot water must be 110F or less. Provide soap at showers.
2.0
30.
Add backflow preventer to hose bibs on pool deck!
0.0
General Comments
Issued year round indoor pool permit.
Wake County Plan Review and Recreational Sanitation Section recommends pools be hyper chlorinated at least twice a month. This activity should be accurately logged on the CPO check list form.
Heater had been turned off for several months. Turned back on day before. Second temperature was from inlet, so heater is slowly moving temperature up.
0.0
5.
Start up. Need readings at least 2x/day 6hrs apart 7days a week. Need at least 2 National/WCES CPO on staff to provide the coverage.
0.0
16.
Watch doors, must be kept selfclosing/latching at all times! Workers coming in and out.
0.0
17.
Do not block deck with furniture when installed.
0.0
24.
No imminent hazard found. Have an electrician evaluate all of the components to determine function.
0.0
25.
Must store all chemicals 12inches off the floor.
2.0
29.
Hot water must be 110F or less.
2.0
30.
Add backflow preventer to hose bibs in pump room.
0.0
General Comments
Issued year round indoor pool permit for 2020/2021 season only!
Wake County Plan Review and Recreational Sanitation Section recommends pools be hyper chlorinated at least twice a month. This activity should be accurately logged on the CPO check list form.
This pool must remain closed until the local and state closure orders currently in effect as a result of the COVID-19 pandemic are terminated.
Pool staff and patrons are strongly encouraged to comply with the most current CDC guidance concerning social distancing related to the COVID-19 pandemic.